1043 Highland Village Trail — PE-Sealed Retaining Wall System

PE-Sealed Cast-in-Place Concrete Retaining Wall System

Division: Division 3 — Structural Concrete

Case Study: 1043 Highland Village Trail, Mableton, GA — Project No. 07339

Published: 2024-03-28

Author: Ducere Construction Services, Inc. — Licensed General Contractor (GA GCCO006711, FL CBC1263793, NASCLA 404696491)


1043 Highland Village Trail — Retaining Wall System

Mableton, Georgia 30126 · Project No. 07339

PE-Sealed Cast-in-Place Concrete Retaining Wall System

This Technical Brief documents the structural engineering and construction specifications for the cast-in-place reinforced concrete retaining wall system at 1043 Highland Village Trail, Mableton, Georgia. The system consists of two walls — Wall #1 (285 linear feet, maximum height 10'-10") and Wall #2 (21 linear feet, maximum height 4'-10") — engineered to manage an extreme grade change across the 0.399-acre site.

All structural retaining wall drawings were prepared and PE-sealed by Yong C. Shao, PE, Georgia Registration No. 26340 (X&Y Engineering Consultants, LLC, Lawrenceville, GA). Construction was issued for permit on March 28, 2024, in accordance with the International Building Code 2018 Edition, Cobb County Construction Ordinances, and ACI 318-14 Building Code Requirements for Structural Concrete.


Project Identification

FieldValue
Project1043 Highland Village Trail, Mableton, GA 30126
Project No.07339
Structural EngineerX&Y Engineering Consultants, LLC
PE SealYong C. Shao, PE — Georgia #26340
Engineer Address2227 Gracehaven Way, Lawrenceville, GA 30043
IssuedMarch 28, 2024 — For Construction
Applicable CodesIBC 2018 · Cobb County Ordinances · ACI 318-14
Civil ReferenceJDM Consultants Grading Plan, 2/25/2024
Owner / GCDucere Construction Services, Inc.
GC LicensesGA GCCO006711 · FL CBC1263793 · NASCLA 404696491
24-HR Contact (GC)Korey Akinbami, (678) 508-6254
JurisdictionUnincorporated Cobb County, Georgia

Scope of Work — Two-Wall System

Wall #1Wall #2
Wall TypeCast-in-place reinforced concrete — CUT & FILL sectionsCast-in-place reinforced concrete — FILL
Total Length285 linear feet21 linear feet
Max. Height (above finish grade)10'-10"4'-10"
Total Vertical Face Area (incl. embedment)2,148 SF71 SF
Elevation RangeEL. 885.6' (footing) to EL. 906.6' (top)EL. 892.5' (footing) to EL. 898.9' (top)
Station RangeSTA 0+00 to STA 2+85; turns at STA 0+24, 0+60, 1+17, 1+36, 2+75STA 0+00 to STA 0+21; turn at STA 0+07
Connection PointTies into building wall — STA 0+00Ties into front porch foundation — STA 0+00
Design Sections5 sections: S-1 through S-5 (varying footing widths and rebar)1 section: S-5 (W=2'-10")

Geotechnical Design Parameters

ParameterRetained SoilFoundation Soil
Soil Unit Weight120 PCF120 PCF
Effective Internal Friction Angle (φ')30 degrees30 degrees
Effective Cohesion (c')0 PSF0 PSF
Equivalent Active Fluid Pressure40 PCF
Equivalent Passive Fluid Pressure360 PCF
Slide Coefficient (μ)0.45
Surcharge0 PSF (no traffic access)
Max. Allowable Bearing Capacity2,500 PSF (design)
Min. Bearing Capacity (footing on undisturbed soil)3,000 PSF (field requirement)
**NOTE:** All design parameters are assumed values per PE design. Contractor must verify soil parameters in the field before pouring concrete. Any discrepancy must be reported to Yong C. Shao, PE (GA #26340) prior to proceeding.

Factors of Safety — Stability Requirements

Failure ModeMinimum F.O.S.Design Basis
Overturning1.5Moment equilibrium — retained soil load vs. wall/footing self-weight
Sliding1.5Passive resistance + base friction vs. active horizontal pressure
Bearing Capacity2.0Maximum footing stress vs. allowable bearing capacity (2,500 PSF)

Wall Dimension & Reinforcing Steel Schedule

SectionHeight (H)W FootingB ToeT WallC HeelE EmbedVert. "V" BarPerp. "P" Bar
S-112'-4"7'-6"2'-6"1'-0"4'-0"1'-6"#5 @ 6" O.C.#4 @ 8" O.C. T&B
S-28'-4"4'-9"1'-6"1'-0"2'-3"1'-0"#5 @ 12" O.C.#4 @ 12" O.C.
S-39'-9"5'-9"1'-6"1'-0"3'-3"1'-0"#4 @ 6" O.C.#4 @ 6" O.C.
S-47'-0"3'-10"1'-3"0'-10"1'-9"1'-0"#4 @ 12" O.C.#4 @ 12" O.C.
S-55'-0"2'-10"1'-0"0'-10"1'-0"1'-0"#4 @ 12" O.C.#4 @ 12" O.C.

Cast-in-Place Concrete Specification

ParameterSpecification
Design StandardsACI 301 — Specifications for Structural Concrete; ACI 318 — Building Code Requirements for Reinforced Concrete; ACI 318-14
Min. Compressive Strength4,000 PSI at 28 days — wall and footing
Air Entrainment5% ± 1.5% at placement
Slump at Placement5" ± 1"
Vertical Control JointsMax. 25' O.C. — Greenstreak Profile Style #714 water stop (or equal); 50% horizontal reinforcement discontinued at joint
ConsolidationMechanical vibrating or spading immediately after placing — ensures concrete free of honeycombing
CuringWet-cured minimum 4 days; 30% solids curing agent applied after wet cure removal
Footing BearingBottom of footing shall bear on original undisturbed soil — min. 3,000 PSF allowable bearing capacity
BackfillFree of organics; compacted to min. 95% max. dry density per ASTM D-698 (Standard Proctor)
Free-Drain Aggregate12" minimum at back of wall — all sections
Weep Holes4" dia. PVC @ 8' O.C. — prevents hydrostatic pressure buildup
Key2"×2" key at footing/wall interface — all sections (see SW-3.0)

Concrete Reinforcement Specification

ParameterSpecification
Steel GradeASTM A615, Grade 60 — all reinforcing steel
Detailing StandardACI 315 — Manual of Standard Practice; CRSI Manual of Standard Practice (latest edition)
FabricationCold bent to shapes and dimensions shown on drawings; no bending after embedded in concrete
Surface ConditionFree from loose rust, scale, dirt, oil, or deleterious coatings that reduce bond
Lap Splice Lengths#4 Bar — 29" minimum; #5 Bar — 36" minimum
Horizontal Bars#4 @ 18" O.C. typical; top horizontal rebar within 6"–12" from top of wall — all sections
Cover — Earth Cast3" clear minimum
Cover — Formed/Exposed2" clear minimum
Cover — Interior/Unexposed3/4" clear minimum
Corner ReinforcingRebar at corner/bend — same size as horizontal wall reinforcement (see SW-4.0)
Footing DowelsMatch vertical bar size and spacing; standard 90° hooks

Contractor Construction Notes (Of Record)

  1. All design and construction shall conform to IBC 2018 Edition.
  2. GC shall verify all dimensions and site conditions; notify engineer of record (Yong C. Shao, PE, GA #26340) of any discrepancies before proceeding.
  3. Contractor shall follow proposed grades per civil site plans in front of and behind the wall. Changes in grade affect structural integrity — notify engineer before proceeding.
  4. GC is responsible for means, methods, techniques, sequences, and procedures to comply with drawings and specifications.
  5. Footing shall bear on original undisturbed soils only — no footing on disturbed material without written authorization from EOR.
  6. Wall #1 transitions from fill to cut configuration at approximately STA 0+60 — verify exact transition station with engineer before forming.
  7. No traffic surcharge assumed in design. If construction equipment operates within H distance of wall (H = wall height), notify EOR immediately for load evaluation.
  8. Provide positive drainage away from wall at all times — contractor responsible for temporary drainage during construction.
  9. All wall turns are per documented survey angles: 115°, 122°, 150°, 123°, 89° at respective stations along Wall #1.
  10. Concrete shall not be placed during freezing temperatures without an engineer-approved cold weather protection plan on file.

Permit Drawing Index — Project No. 07339

SheetTitleScaleDate
SW-1.0Cover Page & Wall Locations — Plan view; scope of work; applicable codesAs Shown3/28/2024
SW-2.0Overall Wall Profiles & Construction Notes — Wall #1 and #2 profiles; geotechnical parameters; concrete and rebar specs1"=30'3/28/2024
SW-2.1Wall #1 Front Face Elevation Views (Enlarged) — STA 0+00 to 1+171"=10'3/28/2024
SW-2.2Wall #1 Front Face Elevation (Cont.) + Wall #2 Front Face Elevation1"=10'3/28/2024
SW-3.0Typical Cross Sections — Fill wall and cut wall; steel schedule (S1–S5)1/2"=1'3/25/2024
SW-4.0Typical Details — Corner reinforcing, control joint, construction joint, stepped footingNTS3/28/2024

Engineer of Record: Yong C. Shao, PE — Georgia Registration No. 26340 · X&Y Engineering Consultants, LLC · 2227 Gracehaven Way, Lawrenceville, GA 30043 · (770) 331-5534 · xyconsulting@gmail.com

All structural retaining wall drawings are PE-sealed and issued for construction. Field conditions deviating from design parameters require written authorization from the EOR before proceeding.


Ducere Construction Services, Inc. · 5925 Mulberry Street, Suite 101 · Austell, GA 30168 · GA GCCO006711 · FL CBC1263793 · NASCLA 404696491 · (404) 565-0631

All data from PE-sealed construction documents, Project No. 07339, 2024.